Airport Cable  

   2491X to BS 6004 Cables

450/750V PVC Insulated, PVC Sheathed Open-door Button Cables (2 core)

FGD200 07VV-F (CU/PVC/PVC 450/750V Class 5)

APPLICATION
The cables are mainly used in open-door button, mass transit underground passenger systems,
airports, petrochemical plants, hotels, hospitals, and high-rise buildings. The cables can be offered
with the ability to restrict the propagation of the flame in the event of a fire.
STANDARDS
Basic design to BS 6004, BS6500
FIRE PERFORMANCE

 

Flame Retardance (SingleVerticalWireTest)**

EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2);

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

 

Reduced FirePropagation(Vertically-mountedbundledwires

&cabletest)**

 

EN60332-3-24 (cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBNC30-004(cat.F2);NFC32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note:
Asterisk * denotes superseded standard
Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC
compound and the cable design.
VOLTAGE RATING
450/750V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to BS 6360 Class 5
Insulation: PVC insulation type TI1 to BS 7655
Filler, binder (if any): PP, PET
Outer Sheath: PVC sheath type T6 to BS 7655

COLOUR CODE
Insulation Colour as per BS7671

 

withearth conductor

withoutearth conductor

2Cores

-

Brown,Blue

3Cores

Yellow/Green,Brown,Blue

Brown,Gray,Black

4Cores

Yellow/Green,Brown,Gray,Black

Brown,Gray,Black,Blue

5Cores

Yellow/Green,Brown,Gray,Black,Blue

Brown,Gray,Black,Blue,Black

above 5 Cores

Yellow/Green,BlackNumbers

Black Numbers

Outer sheath: Black or as order
Physical AND THERMAL PROPERTIES
Operating temperature: -15º C to +70º C
Short circuit temperature: +160º C
Minimum bending radius: 4x Overall Diameter
Insulation resistance: 20 MΩxkm
CONSTRUCTION PARAMETERS

Conductor

fGD20007VV-f

No.of
CoreX
Cross
Section

No./
Nomina l
Diameter
of
Strands

Conductor
Diameter

Nominal
Insulation Thickness

Nominal
Sheath Thickness

Nominal
Overall Diameter

Max.DC resistance ofconductor

@20°C

 

Approx. Weight

Noxmm2

No./mm

mm

mm

mm

mm

Ω/km

kg/km

2x1.0

32/0.20

1.32

0.6

0.9

7.0

18.1

66

Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)

Conductor cross- sectional area

Reference Method4(enclosed inconduit in thermallyinsulatingwalletc)

Reference
Method3 (enclosed inconduit ona wallorintrunkingetc)

Reference
Method1
(clipped direct)

Reference
Method11
(onaperforated cabletray,
horizontalor
vertical)

Reference
Method 12
(freeair)

Horizontal
flat spaced

Vertical
flat spaced

Trefoil

2
cables, single- phase
a.c.ord.c.

3 or
4cables, 3-phasea.c.

2
cables, single- phase
a.c.ord.c

3 or 4cables, 3-phasea.c.

2cables, single- phase
a.c.or
d.c. flat
andtouching

3 or 4cables, 3-phase
a.c. flat
andtouching or trefoil

2 cables, single- phase
a.c.or
d.c.orflat and touching

3 or 4cables, 3-phase
a.c. flat
andtouching or trefoil

2cables, single- phase
a.c.ord.c.or 3cablesthree phase

2cables, single- phase
a.c.ord.c.or 3
cables three phase

3cables, trefoil
3-phasea.c.

1

2

3

4

5

6

7

8

9

10

11

12

mm2

A

A

A

A

A

A

A

A

A

A

A

1.0

13

-

-

-

15

-

-

-

-

-

-

Voltage Drop (Per Amp Per Meter)

Nominal
Cross
ection
Area

2cables d.c.

2cables,
single-phasea.c.

3or 4cables,3-phase a.c.

Ref.Methods3
and 4 (enclose
dinconduitetc, inoron a wall)

Ref.Methods1
and11(clippeddirector ontraystouching)

Ref.Methods3
and 4 (enclosedinconduitetc ,inoron a wall)

Ref.Methods1,

Ref.Methods1and11

 

11 and12 (intrefoil)

 

 

(Flat and touching)

1

2

3

4

5

6

7

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

1.0

46

46

-

-

-

-

Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance